| Posted by Deb on February 18, 2004 at 19:51:01: | |
|---|---|
| In response to Re: Venting ? | |
|
: Have a roughed in basement bathroom with no vent pipe : to tie into. Looked at old pictures of our house construction and saw that in the 1st floor powder room there is a 2 in vent pipe from vanity sink that runs somewhere up to attic. The powder room is almost on top of the basement bathroom. My question: Can I break into the powder room wall and run a T back down to basement to provide a vent path for the tub,toilet and vanity down there? Is it legal to tie 2 in vent pipe from the basement into another 2 in pipe which serves the powder room? : Thanks! Yes you can do this. It will need to be tied in 6" above the highest fixture this vent serves. |
|
| Replies to this post |
| There are none. |