In Reply to: Underfloor Heating Probs posted by Richard Cloot on March 01, 1999 at 06:45:20:
How did you make this connection?
Is it tapped off of the hot water baseboard loop or from existing radiant floors?
Typically if adding a zone of radiant heat, it needs to have a separate circ with a mixing valve so as the floor does not get too hot.